Calculate wire gauge (AWG), maximum current capacity, or voltage drop for DC electrical circuits. Free online DC wire size calculator with support for copper and aluminum wires. Perfect for solar panels, batteries, and DC power systems.
Calculate wire gauge (AWG), current capacity, or voltage drop for DC electrical circuits
Formula:
R = (ρ × L × 2) / A, V_drop = I × R
Note: Length is for one-way distance. Calculator uses round-trip (×2) for resistance.
Copy the code below to embed this calculator on your website
Proper wire sizing is critical for DC electrical systems, including solar panel installations, battery banks, automotive applications, and low-voltage DC power distribution. Unlike AC circuits, DC circuits have unique considerations that make accurate wire sizing calculations essential for safety, efficiency, and optimal performance. Our DC Wire Size Calculator makes it easy to determine the appropriate American Wire Gauge (AWG) size, calculate maximum current capacity, or determine voltage drop specifically for direct current (DC) electrical installations.
DC wire size directly affects electrical resistance, current-carrying capacity, and voltage drop. Using undersized wires in DC circuits can lead to excessive voltage drop, reduced efficiency, overheating, and potential fire hazards. Our calculator helps ensure you select the correct wire size for your specific DC application, whether you're working with 12V automotive systems, 24V solar installations, or any other DC voltage.
Our DC Wire Size Calculator offers three different calculation modes specifically designed for DC circuits:
Select your calculation mode, choose wire material (copper or aluminum), enter the known values, and click Calculate to get instant results with detailed step-by-step solutions optimized for DC applications.
DC wire size calculations are based on electrical resistance and Ohm's law, which applies directly to DC circuits:
R = (ρ × L × 2) / A
Where: R = resistance (Ω), ρ = resistivity (Ω·m), L = length (m), A = cross-sectional area (m²)
Note: Length is multiplied by 2 for round-trip (out and back) in DC circuits
V_drop = I × R
Where: V_drop = voltage drop (V), I = current (A), R = resistance (Ω)
This formula applies directly to DC circuits without power factor considerations
AWG is a standardized wire gauge system used in North America. Lower AWG numbers indicate larger wire diameters:
While the fundamental formulas are similar, DC wire sizing has important differences from AC:
DC wire size calculations are essential in numerous electrical applications:
It's crucial to use consistent units in your DC wire size calculations:
Tip: Our calculator automatically handles unit conversions for length. The calculator uses round-trip distance (length × 2) for resistance calculations, which is standard practice for DC voltage drop calculations.
A 12V solar panel system needs to carry 20A over 50 feet with a maximum 3% voltage drop. What wire size is needed?
Maximum voltage drop: 12V × 0.03 = 0.36V
Required resistance: R = 0.36V / 20A = 0.018 Ω
Required area: A = (1.68×10⁻⁸ Ω·m × 15.24 m × 2) / 0.018 Ω ≈ 28.5 mm²
Result: 6 AWG wire (13.3 mm²) or larger is recommended for this DC application
What is the maximum current for 10 AWG copper wire over 25 feet with a 2% voltage drop at 24V DC?
10 AWG area: 5.26 mm²
Resistance: R = (1.68×10⁻⁸ × 7.62 m × 2) / (5.26×10⁻⁶ m²) ≈ 0.049 Ω
Maximum voltage drop: 24V × 0.02 = 0.48V
Maximum current: I = 0.48V / 0.049 Ω ≈ 9.8 A
What is the voltage drop for 14 AWG copper wire carrying 10A over 15 feet at 12V DC?
14 AWG area: 2.08 mm²
Resistance: R = (1.68×10⁻⁸ × 4.57 m × 2) / (2.08×10⁻⁶ m²) ≈ 0.074 Ω
Voltage drop: V_drop = 10A × 0.074 Ω = 0.74 V (6.2%)
The choice between copper and aluminum wires affects DC calculations:
Aluminum wire typically requires one or two AWG sizes larger than copper for the same current capacity in DC circuits. Always use the correct material resistivity in your calculations.
Acceptable voltage drop for DC circuits depends on the application:
Excessive voltage drop in DC circuits can cause equipment malfunction, reduced efficiency, battery drain, and safety issues. Always consult local electrical codes and equipment specifications for specific requirements.
DC wire sizing is simpler because there's no power factor or skin effect to consider. However, DC systems often operate at lower voltages (12V, 24V, 48V), making voltage drop more critical. The fundamental formulas (Ohm's law) are the same, but DC calculations don't require AC-specific considerations like power factor correction.
DC systems often operate at lower voltages (12V, 24V, 48V) compared to AC systems (120V, 240V). A 1V drop in a 12V system is 8.3%, while a 1V drop in a 120V system is only 0.83%. This makes proper wire sizing even more important for DC applications to maintain system efficiency and equipment performance.
Solar panel wire sizing depends on current, voltage, distance, and acceptable voltage drop. Common sizes include 10 AWG for smaller systems, 8 AWG for medium systems, and 6 AWG or larger for high-current or long-distance runs. Always calculate based on your specific requirements using our DC Wire Size Calculator.
Yes! Our DC Wire Size Calculator is perfect for 12V automotive applications. Enter 12V as your supply voltage, your current requirements, acceptable voltage drop (typically 3-5% for automotive), and wire length. The calculator will determine the appropriate wire gauge for your automotive electrical system.
Copper is more common for DC applications due to better conductivity and easier installation. Aluminum is lighter and less expensive but requires larger gauge for the same current. For most DC applications, especially automotive and solar, copper is preferred. Aluminum is typically used in larger commercial DC installations where cost and weight are significant factors.
For DC battery systems, a voltage drop of 2-3% is typically acceptable. This preserves battery efficiency and ensures proper equipment operation. For critical applications or long wire runs, you may want to keep voltage drop below 2%. Always consult your battery and equipment specifications for specific requirements.
Wire length is multiplied by 2 because DC current flows from the source (battery, solar panel) to the load and back (round trip). The total resistance includes both the outgoing wire and the return wire, so we use 2× the one-way distance for accurate voltage drop calculations in DC circuits.
Always consult local electrical codes and safety standards. Consider: ambient temperature (affects wire ampacity), wire bundling (reduces current capacity), installation method, safety margins (typically 20-25% above calculated requirements), and equipment specifications. When in doubt, consult a licensed electrician or electrical engineer familiar with DC systems.
Proper DC wire sizing is essential for electrical safety, efficiency, and optimal performance in DC electrical systems. Our DC Wire Size Calculator simplifies these calculations, making it easy to determine appropriate wire gauge, current capacity, and voltage drop for DC installations including solar panels, battery systems, automotive applications, and more.
Ready to explore more electrical concepts? Check out our other calculators like the Wire Size Calculator for general wire sizing, or the Parallel Resistor Calculator for DC circuit analysis that often complements wire sizing work.